Versions - Siemens SIRIUS 3RT Series System Manual

Modular system for the control cabinet
Hide thumbs Also See for SIRIUS 3RT Series:
Table of Contents

Advertisement

SIRIUS 3RV2 motor starter protectors
4.9 Accessories
4.9.11.2

Versions

3-phase busbar versions
For the infeed of several motor starter protectors with screw terminals for side-by-side
mounting on DIN rails, insulated, with touch protection
Table 4- 30
3-phase busbars
Order no.
Number of motor starter protectors that can be connected
Modular spacing
[mm]
3RV19 15-1..
45
3RV19 15-2..
55
3RV19 15-3..
63
Not suitable for 3RV21 motor starter protectors for motor protection with overload relay function and for 3RV27 and
1)
3RV28 circuit breakersconforming to UL 489/CSA C22.2 No.5-02.
3-phase infeed terminal:
The infeed terminal supports larger conductor cross-sections than is the case with direct
connection on the motor starter protector.
● Infeed terminal from above
● Infeed terminal from below
Note
Space requirements of the infeed terminal
The infeed terminal with connection from below is connected instead of a motor starter
protector. You will, therefore, need to take the space requirements into account when
configuring the 3-phase busbars.
1)
438
1)
Without lateral
accessories
2 / 3 / 4 / 5
-
-
Order no.
Conductor cross-section
Solid or
stranded
mm²
Connection from above
3RV29 25-5AB
2.5 to 16
Connection from below
3RV29 15-5B
2.5 to 16
This terminal is connected in place of a switch, please take the space requirement into
account.
Incl. auxiliary
release
Incl. lateral
auxiliary switch
-
-
2 / 3 / 4 / 5
-
-
2 / 4
Finely
AWG cables,
stranded with
solid or
end sleeve
stranded
mm²
AWG
2.5 to 16
10-4
1)
2.5 to 16
10-4
System Manual, 01/2011, A8E56203870002-03
Rated current I
690 V
63
63
63
Tightening
For motor
torque
starter protector
size
Nm
3 to 4
S00, S0
Input: 4,
S00, S0
Output:
2 to 2.5
SIRIUS Innovations