SIRIUS 3RV2 motor starter protectors
4.10 Technical data
4.10.7
Auxiliary releases
Power input
During pick-up
- Alternating voltages
- Direct voltages
During continuous operation
- Alternating voltages
- Direct voltages
Response voltage
Tripping
Pick-up
Maximum opening time
4.10.8
Short-circuit protection for auxiliary and control circuits
gL/gG melting fuses
Miniature circuit breaker, C characteristic
Prospective short-circuit current < 0.4 kA
1)
458
Undervoltage release
VA/W
20.2 / 13
W
20
VA/W
7.2 / 2.4
W
2.1
V
0.35 to 0.7 x U
V
0.85 to 1.1 x U
ms
20
Undervoltage release
A
10
A
6
1)
Shunt release
20.2 / 13
13 ... 80
--
--
0.7 to 1.1 x U
s
--
s
Shunt release
System Manual, 01/2011, A8E56203870002-03
s