4.2.2

Versions

Device versions
● Motor starter protectors, standard version (3RV20)
Overload and short-circuit protection
● Motor starter protectors with relay function (3RV21)
Short-circuit protection and auto-RESET in the event of overload in one device
● MSP for starter combinations (3RV23)
Short-circuit protection only
Combined with overload relay, large setting ranges and auto-RESET
● MSP for transformer protection (3RV24)
Standard version for transformers
● Approved devices for North America according to UL489 (3RV27/3RV28)
Overload/short-circuit protection and transformer protection
Sizes
3RV2 motor starter protectors are available in two sizes, S00 and S0.
The table below lists the sizes and the corresponding maximum rated current at a voltage of
400 V AC. The last column of the table indicates the maximum power of the three-phase
motor which is suitable for the relevant size.
Table 4- 2
Size
S00
S0
3RV21: 65 mm
1)
3RV20 and 3RV23 only
2)
Number of poles
3RV2 motor starter protectors have 3 poles.
SIRIUS Innovations
System Manual, 01/2011, A8E56203870002-03
Motor starter protector sizes
Width
Max. rated current
45 mm
16 A
1)
45 mm
40 A
1)
2)
SIRIUS 3RV2 motor starter protectors
4.2 Product description
Power of three-phase motor
7.5 kW
18.5 kW