Diagnostics in the "RUN" menu

Information on the display
Display information
The display can basically be divided into three different display values/symbols.
3
(1)
(2)
(3)
Meaning of the information on the display (with Mem = no)
Symbol
12.5A
n x I▲
I>>
L
SIRIUS Innovations
System Manual, 01/2011, A8E56203870002-03
1
2
Current measured value or fault symbol
Type of monitoring
Symbols for the CO contact (right) and the semiconductor output (left)
Meaning
Displays the measured current
Flashing: Current is above the set blocking current
Flashing: Fault current detected
Flashing: Cable break/phase failure detected
Flashing: Incorrect phase sequence detected
Not flashing: Relay contact 31/32 open, relay contact 31/34 closed
Flashing: Delay time (ON or tripping delay) running
Masked out: Relay contact 31/32 closed, relay contact 31/34 open
Not flashing: Semiconductor output closed, supply voltage connected
Q
Flashing: Delay time (ON or tripping delay) running
Masked out: Semiconductor output open, supply voltage not switched through
Monitoring for current overshoot
Monitoring for current undershoot
Window monitoring (monitoring for current overshoots and undershoots)
Current is in correct range
A current overshoot has occurred
A current undershoot has occurred
SIRIUS 3RR2 current monitoring relays