SIRIUS 3RF34 solid-state switching devices

3.11 Technical data

3.11
Technical data
3.11.1

General data

Table 3- 23
Solid-state switching devices - General data
General data
Ambient temperature
Operation, derating as of 40 °C
Storage
Installation altitude
Shock resistance according to DIN IEC 60068-2-27
Vibration resistance; acc. to DIN IEC 60068-2-6
Degree of protection
Electromagnetic compatibility (EMC)
Emitted interference acc. to DIN IEC 60947-4-2
-
Conducted interference
-
Emitted high-frequency interference
voltage
Immunity
2)
-
Electrostatic discharge acc. to
DIN IEC 61000-4-2 (corresponds to
severity 3)
-
Induced conducted RF fields
acc. to DIN IEC 61000-4-6
-
High-frequency, electromagnetic
fields acc. to DIN IEC 61000-4-3
-
Burst acc. to DIN IEC 61000-4-4
-
Surge acc. to DIN IEC 61000-4-5
Connection type
Solid-state contactor
Solid-state reversing contactor
350
°C
- 25 ... + 60
°C
- 55 ... + 80
m
0 ...1000;
at > 1,000 m seek advice from Technical Assistance
(www.siemens.com/lowvoltage/technical-assistance)
g
/ms
15/11
g
2
IP20
Class A for industrial environments
Class A for industrial environments
kV
Contact discharge: 4; air discharge: 8; behavior criterion 2
MHz
0.15 ... 80, 140 dBμV, behavior criterion 1
MHz
80 ... 3,000; test level 10 V/m; behavior criterion 1
kV
2/5.0 kHz; behavior criterion 2
kV
Conductor - protective conductor 2; conductor - conductor:
3)
1; behavior criterion 2
Screw-type and spring-loaded
Screw-type connection system
1)
SIRIUS Innovations
System Manual, 01/2011, A8E56203870002-03