"Manual motor controller", group installation
3RV2 motor starter protector as "Manual Motor Controller"
Upstream short-circuit protection is always implemented if the motor starter protector is used
as a "Manual Motor Controller". This requires approved fuses (according to UL 248) or a
circuit breaker (according to UL 489/CSA C22.2 No. 5-02). These devices must be
dimensioned according to the National Electrical Code (UL) or Canadian Electrical Code
(CSA) installation regulation respectively.
The file numbers for the approval of the 3RV as a manual motor controller are as follows:
● UL File No. 47705, CCN: NLRV
● CSA Master Contract 165071, Product Class: 3211 05
Motor starter protector
Type
Size S00
3RV20 11, 3RV21 11, 3RV23 11, 3RV24 11
FLA
12.5 A, 600 V
Size S0
3RV20 21, 3RV21 23, 3RV23 21, 3RV 21, 3RV24 21
FLA
hp-rating= power in horse power(maximum motor power).
1)
FLA= Full Load Amps/motor full-load current
2)
Rated current
In
A
Size S00
0.16 ... 1.25
1.6
2
2.5
3.2
SIRIUS Innovations
System Manual, 01/2011, A8E56203870002-03
V
max. 16 A, 480 V
115
2)
200
230
460
575/600
max. 40 A, 480 V
115
2)
200
230
460
575/600
240 V AC
UL
Ibc
kA
65
65
65
65
65
480 V AC
CSA
UL
Ibc
Ibc
kA
kA
65
65
65
65
65
65
65
65
65
65
SIRIUS 3RV2 motor starter protectors
4.10 Technical data
hp-rating
for FLA
1)
2)
max.
1-phase
3-phase
1
2
2
3
2
5
--
10
--
10
3
5
5
10
7 1/2
10
--
30
--
--
600 V AC
CSA
UL
Ibc
Ibc
kA
kA
65
30
65
30
65
30
65
30
65
30
CSA
Ibc
kA
30
30
30
30
30
469