Technical data

7.1

All device versions

7.1.1

Rated conditions

Rated conditions
Ambient conditions
Ambient temperature
Permissible ambient temperature for operation
Maximum permissible height above sea level
Relative humidity
Degree of pollution
Overvoltage category
Degree of protection
1)
Vibration resistance
Harmonic oscillations (sine) according to
IEC 60068-2-6
Bump (half-sine) according to
IEC 60068-2-27
Noise (controlled digitally) according to
IEC 60068-2-64
Recommended range of continuous operation of the entire
control valve
Climate class
Storage
Transport
Max. impact energy 1 Joule for enclosure with inspection window 6DR5..0 and 6DR5..1 or max. 2 Joule for 6DR5..3
1)
2)
At ≤ -10 °C (≤ 14 °F) the display refresh rate of the indicator is limited.
The following applies to order suffix (order code) -Z M40: -40 ... +80 °C (-40 ... +176°F)
3)
See also
Proper mounting (Page 19)
Ambient temperature (Page 62)
SIPART PS2 (6DR5...)
Compact Operating Instructions, 11/2022, A5E03436620-AG
 
For use indoors and outdoors.
In hazardous areas, observe the maximum permissible am‐
bient temperature corresponding to the temperature class.
-30 ... +80 °C (-22 ... +176 °F)
2)3)
Up to 2000 m
0 ... 100%
2
II
IP66 / Type 4X to UL 50E
 
3.5 mm (0.14"), 2 ... 27 Hz, 3 cycles/axis
98.1 m/s² (321.84 ft/s²), 27 ... 300 Hz, 3 cycles/axis
150 m/s² (492 ft/s²), 6 ms, 1000 shocks/axis
10 ... 200 Hz; 1 (m/s²)²/Hz (3.28 (ft/s²)²/Hz)
200 ... 500 Hz; 0.3 (m/s²)²/Hz (0.98 (ft/s²)²/Hz)
4 hours/axis
≤ 30 m/s² (98.4 ft/s²) without resonance peak
According to IEC/EN 60721-3
1K5, -40 ... +80 °C (-40 ... +176 °F)
2K4, -40 ... +80 °C (-40 ... +176 °F)
7