SIRIUS 3RV2 motor starter protectors
4.9 Accessories
Mounting the disconnector module
Table 4- 20
Step
1
2
3
4
5
6
7
8
420
Mounting the disconnector module
Operating instruction
Set the rotary button on the motor
starter protector to O.
Remove the protective cover from the
terminal lugs on the disconnector
module.
Set the disconnector module down on
the motor starter protector. Make sure
that the terminal lugs on the
disconnector module slot into the
corresponding openings.
Slide the closing lockout down.
Screw the main conductor terminals
tight on the motor starter protector.
Slide the closing lockout up.
Set the rotary button on the motor
starter protector to I.
Secure the disconnector module so
that the isolating plug cannot be
removed when the motor starter
protector is active.
Figure
System Manual, 01/2011, A8E56203870002-03