Sirius 3Ra28 Function Modules For Mounting On Sirius 3Rt2 Contactors - Siemens SIRIUS 3RT Series System Manual

Modular system for the control cabinet
Hide thumbs Also See for SIRIUS 3RT Series:
Table of Contents

Advertisement

System overview
1.7 Components and combinations
1.7.5.1

SIRIUS 3RA28 function modules for mounting on SIRIUS 3RT2 contactors

3RA28 function modules for mounting on 3RT2 contactors
SIRIUS 3RA28 function modules for mounting on SIRIUS 3RT2 contactors enable the
control circuit wiring to be reduced significantly. With star-delta (wye-delta) starters, for
example, they replace the control circuit wiring in its entirety.
Table 1- 18
Area
Functions
Dimensioning and
design
Mounting
advantages
Application
areas/customer
benefits
66
3RA28 function modules for mounting on 3RT2 contactors
Customer benefits
Direct-on-line, reversing, and star-delta (wye-delta) start
Time-delayed switching of contactors (0.05 to 100 s)
ON-delay and OFF-delay versions
Star-delta (wye-delta) function module without extra control circuit wiring
Switch position indication for the contactor via a mechanical plunger
Only one version for S00 and S0
Suitable for control voltages of 24 to 240 V AC/DC
Contactor coil controlled via semiconductor output
Star-delta (wye-delta) switchover 0.5 to 60 s
Star-delta (wye-delta) changeover delay: 50 ms
Easy plug-on assembly of a starter, without tools
Removable terminals
Screw-type and spring-loaded terminals
Assembly of star-delta (wye-delta) starters, including timing function and
electrical interlock, without additional wiring
Universal applicability thanks to wide voltage and time ranges
SIRIUS Innovations
System Manual, 01/2011, A8E56203870002-03