SIRIUS 3RU2/3RB3 overload relays
5.10 Technical data
Type
Size
Width
Connection type
Connection screw
Operating tool
Specified tightening torque
Usable ring cable lugs
DIN 46234 without insulating sleeve
DIN 46225 without insulating sleeve
DIN 46237 with insulating sleeve
JIS C2805 type R without insulating sleeve
JIS C2805 type RAV with insulating sleeve
JIS C2805 type RAP with insulating sleeve
If two different conductor cross-sections are being connected to one clamping point, both cross-sections must be
1)
located in the range indicated. If identical cross-sections are used, this restriction does not apply.
2)
d
d
542
3
2
3RU21 16
S00
45 mm
Ring cable lug connection
M3, Pozidriv size 2
mm
∅ 5 to 6
Nm
0.8 to 1.2
mm
d
= min. 3.2,
2)
2
d
= max. 7.5
2)
3
3RU21 26
S0
45 mm
M4, Pozidriv size 2
∅ 5 ... 6
2 to 2.5
d
= min. 4.3,
2)
2
d
= max. 12.2
2)
3