SIRIUS 3RT2 contactors/contactor assemblies
2.8 Technical data
Type
Size
Actuation
DC operation
Switching on
- ON-delay NO contact
- OFF-delay NC
contact
Switching off
- OFF-delay NO
contact
- ON-delay NC contact
Arcing time
Dependency of switching frequency z'on operational current I' and
operational voltage U'
z' = z ⋅ I
/I' ⋅ (U
/U')1.5 ⋅ 1/h
e
e
The use of the additional load module 3RT2916-1GA00 is recommended at higher residual currents.
1)
The OFF-delay times of the NO contacts and the ON-delay times of the NC contacts increase if the contactor coils are
2)
attenuated against voltage peaks (suppression diode 6x to 10x; diode combination 2x to 6x; varistor +2 to 5 ms).
276
0.8 ... 1.1 x U
S
1.0 x U
S
Minimum operating time 3RH24
0.8 ... 1.1 x U
S
1.0 x U
S
0.8 ... 1.1 x U
S
1.0 x U
S
Minimum operating time 3RH24
0.8 ... 1.1 x U
S
1.0 x U
S
3RH2.
S00
ms
30 ... 100
ms
20 ... 50
ms
≥ 100
ms
25 ... 90
ms
30 ... 45
ms
7 ... 13
ms
7 ... 12
ms
≥ 30
ms
13 ... 19
ms
13 ... 18
ms
10 ... 15
System Manual, 01/2011, A8E56203870002-03
SIRIUS Innovations