Siemens SIRIUS 3RT Series System Manual page 466

Modular system for the control cabinet
Hide thumbs Also See for SIRIUS 3RT Series:
Table of Contents

Advertisement

SIRIUS 3RV2 motor starter protectors
4.10 Technical data
Rated current I
Up to 440 V
n
I
cuIT
A
kA
Size S0
16
2
20
2
22
2
25
2
28
2
32
2
36
2
40
2
No backup fuse required, as short-circuit-proof up to 100 kA
1)
10 % overvoltage
2)
5 % overvoltage
3)
Backup fuse only required if short-circuit current at installation location is > I
4)
Alternatively, fuseless limiter combinations can be used for 690 V AC
5)
Overvoltage category II applies for applications in IT systems > 600 V
6)
466
/460 V
AC
Up to 500 V
2)
3)
Max. fuse
I
cuIT
(gL/gG)
4), 5)
A
kA
50
2
50
2
50
2
50
2
63
2
63
2
63
2
63
2
/525 V
AC
2)
3)
Max. fuse (gL/gG)
4), 5)
A
50
50
50
50
63
63
63
63
cuIT
System Manual, 01/2011, A8E56203870002-03
Up to 690 V
AC
6)
I
Max.
cuIT
fuse
(gL/gG)
4)
kA
A
1.5
40
1.5
50
1.5
50
1.5
50
1.5
63
1.5
63
1.5
63
1.5
63
SIRIUS Innovations