Mounting; Mounting Options; Minimum Clearances And Mounting Positions; Mounting/Disassembly - Siemens SIRIUS 3RT Series System Manual

Modular system for the control cabinet
Hide thumbs Also See for SIRIUS 3RT Series:
Table of Contents

Advertisement

8.6

Mounting

8.6.1

Mounting options

3RR2 current monitoring relays are matched to 3RT2 contactors and 3RF34 (S0) solid-state
contactors in terms of their electrical and mechanical features. As a result, direct mounting
can be achieved easily.
Alternatively, the devices can also be installed individually in the case of stand-alone
assembly or if a 3RU2/3RB3 overload relay is being used at the same time.
8.6.2

Minimum clearances and mounting positions

Minimum clearance
A minimum lateral clearance of > 6 mm must be maintained from grounded parts.
Mounting position
It can be mounted in any position.
8.6.3

Mounting/Disassembly

Direct mounting on 3RT2 contactor/3RF34 (S0) solid-state contactor
The diagram below shows an example mounting scenario based on mounting the
3RR21 analog setting current monitoring relay, size S0, on the 3RT2 contactor.
Table 8- 3
Mounting of 3RR2 current monitoring relay, screw-type connection system (S0)
Step
Operating instruction
1
Push the current monitoring relay into the
contactor from below. Attach the two hooks
on the current monitoring relay to the two
openings on the rear of the contactor. This
pushes the main current contacts into the
corresponding terminals on the contactor.
2
Tighten the screws on the contactor with a
Pozidriv size 2 (S00) or Pozidriv size 3 (S0)
screwdriver (tightening torque 0.8 to 1.2 Nm).
Check that the cable is clamped tight.
SIRIUS Innovations
System Manual, 01/2011, A8E56203870002-03
SIRIUS 3RR2 current monitoring relays
Figure
8.6 Mounting
699