"Self-protected combination motor controller (type E)" (up to 32 A)
3RV20 motor starter protector as "Self-Protected Combination Motor Controller (Type E)"
For approval according to UL 508, a clearance of 1 inch and a creepage distance of 2 inches
are required on the line side for a "Self-Protected Combination Motor Controller".
Therefore, 3RV20 motor starter protectors in size S00/S0 are approved according to UL 508
together with the terminal block (order no. 3RV29 28-1H) or phase barriers (order
no. 3RV2928-1K).
CSA approval does not require extended clearances and creepage distances. The terminal
blocks or phase barriers can, therefore, be omitted for use as a "Self-Protected Combination
Motor Controller" according to the CSA.
3RV20 motor starter protectors are approved as "Self-Protected Combination Motor
Controller" under the following file numbers:
● UL File No. E156943, CCN: NKJH.
● CSA Master Contract 165071, Product Class: 3211 08.
Motor starter protector
Type
Size S00
3RV20 11
FLA
16 A, 480 V
12.5 A, 600 V
Size S0
3RV20 21
FLA
32 A, 480 V
hp-rating= power in horse power(maximum motor power).
1)
FLA= Full Load Amps/motor full-load current
2)
SIRIUS Innovations
System Manual, 01/2011, A8E56203870002-03
V
max.
115
2)
200
230
460
575 / 600
max.
115
2)
200
230
460
575/600
SIRIUS 3RV2 motor starter protectors
4.10 Technical data
hp-rating
for FLA
1)
2)
max.
1-phase
3-phase
1
2
2
3
2
5
--
10
--
10
2
5
3
7 1/2
5
10
--
20
--
--
473