Siemens SIRIUS 3RT Series System Manual page 286

Modular system for the control cabinet
Hide thumbs Also See for SIRIUS 3RT Series:
Table of Contents

Advertisement

SIRIUS 3RT2 contactors/contactor assemblies
2.8 Technical data
Table 2- 125 Load side - Coupling link 3RH2924-1GP11
Type
Size
Load side
Mechanical durability
Electrical durability at I
e
Switching frequency
ON time
OFF time
Bounce time
Contact material
Switching voltage
Permissible residual current of electronics (with 0
signal)
Rated operational currents
current I
th
Rated operational currents I
categories
AC-15
- At 24 V
- At 110 V
- At 230 V
DC-13
- At 24 V
- At 110 V
- At 230 V
Switching current with resistive load acc. to
DIN EN 60255 (relay standard) and DIN EN 60947
AC-12
- At 24 V
- At 110 V
- At 230 V
DC-12
- At 24 V
- At 110 V
- At 230 V
Capacitive loads can result in micro-welding on the contacts.
1)
286
in million
operating
cycles
in million
operating
cycles
Operating
cycles
Conventional thermal
1)
acc. to DIN EN 60947 utilization
e
3RH2924-1GP11
Coupling link for mounting on contactors
acc. to IEC 60947/DIN EN 60947
20
0.1
h
5000
-1
ms
Approx. 7
ms
Approx. 4
ms
Approx. 2
AgSnO
V AC/DC
24 ... 250
mA
2.5
A
6
A
3
A
3
A
3
A
1
A
0.2
A
0.1
A
6
A
6
A
6
A
6
A
0.3
A
0.2
1)
SIRIUS Innovations
System Manual, 01/2011, A8E56203870002-03

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents