Output Functions

Commercial burglary alarm systems require bell circuits to be programmed for a minimum timeout of
16 minutes.
Commercial fire alarm systems require bell or indicating circuits to be supervised. Polarized fire-
indicating devices must be used.
U L
Commercial fire alarm systems require bell or indicating circuits to be programmed for a minimum
timeout of 5 minutes.
Residential fire alarm systems require bell or indicating circuits to be programmed for a minimum
timeout of 4 minutes.
Each output can be programmed for one of the following functions:
Description
Fire Alarm
Holdup
Alarm
Supervisory
Alarm
Alarm in any
BA Group
Alarm in a
Selected BA
Group
BA1 Alarm
BA2 Alarm
BA3 Alarm
BA4 Alarm
BA5 Alarm
BA6 Alarm
BA7 Alarm
BA8 Alarm
6-2
Function
The output activates and latches when an alarm occurs at any fire alarm point. If
all fire alarm points have restored to normal, the output resets by entering a
RESET command at any operating panel.
Note: It takes 40 seconds before the output resets.
The output activates when either of the following occurs:
• An alarm condition occurs at a holdup point. It resets when the holdup device is
restored.
• A hostage ID code is entered. The output resets when the operating panel
deactivates (after 45 seconds).
The output activates when an alarm condition occurs at any supervisory point. It
resets when all supervisory devices are restored.
The output activates when an entry alarm occurs in any BA group during Nite Set.
The output resets when the involved BA group is changed to Day Set. This form of
output control can be used for direct-connect type applications.
This is the same as the above option except that it is used for an alarm in a single
selected BA group rather than for any BA group.
Output is normally operated. It releases when an entry alarm occurs in BA1 during
Nite Set. It returns to operated condition when either the programmed bell time
ends and the points are secure or when BA1 is returned to Day Set.
Same function as BA1 Alarm, except it relates to BA2.
Same function as BA1 Alarm, except it relates to BA3.
Same function as BA1 Alarm, except it relates to BA4.
Same function as BA1 Alarm, except it relates to BA5.
Same function as BA1 Alarm, except it relates to BA6.
Same function as BA1 Alarm, except it relates to BA7.
Same function as BA1 Alarm, except it relates to BA8.