ADT FOCUS 200 PLUS Installation And Setup Manual page 128

Commercial fire and burglary security system with scheduling
Hide thumbs Also See for FOCUS 200 PLUS:
Table of Contents

Advertisement

FOCUS 200 PLUS Installation and Setup Guide
1.
In table 4, enter devices used on the RS-485 Bus #1. Calculate standby and alarm currents, then
add to get RS-485 Bus #1 current subtotal.
Table 4: RS-485 BUS #1 CURRENT LOAD
Device Model #
2.
In table 5, enter devices used on the RS-485 Bus #2. Calculate standby and alarm currents, then
add to get RS-485 Bus #2 current subtotal.
Table 5: RS-485 BUS #2 CURRENT LOAD
Device Model #
12-10
Device Current X # of Units =
RS-485 Bus #1 Subtotal
(terminals 19 & 20 - 1.0A max.)
Device Current X # of Units =
RS-485 Bus #2 Subtotal
(terminals 23 & 24 - 1.0A max.)
Total Current
Standby
Alarm
Total Current
Standby
Alarm