Figure 7-1: Installing The 472402A Backup Dialer - ADT FOCUS 200 PLUS Installation And Setup Manual

Commercial fire and burglary security system with scheduling
Hide thumbs Also See for FOCUS 200 PLUS:
Table of Contents

Advertisement

Step
Action
2
Install an RJ31X jack within the proximity of the control unit. Install a second one if you
are using the backup dialer.
3
Run telephone company lines to the jack(s) and connect them to the red and green
terminals. Connect to the brown and gray terminals all premises phones that use the
same telephone line(s).
4
Connect the main dialer to the RJ31X jack using the RJ31X Cable supplied.
5
Mount the backup dialer to the main PCB as shown in Figure 7-1.
6
Connect the backup dialer to the main PCB J6 connector using a ribbon cable (supplied).
Do not run the ribbon cable underneath the backup dialer PC board.
The J6 header is static-sensitive. Make connections to the header with the
power to the control unit off and after grounding yourself.
7
Connect the backup dialer to the RJ31X jack, using the RJ31X Cable supplied.
8
Connect the earth ground screw on the backup dialer to the earth ground screw
(terminal 3 or 4) on the main PCB using 16 AWG wire.
To prevent the risk of shock, disconnect phone lines at the RJ31X jack before servicing the panel.
OPTIONAL 472402A
BACK-UP DIALER
MODULE
BACK-UP
LINE SEIZE
LED (GREEN)
CONTROL
PANEL
RS-485 #2
RS-485 #1
17
18
19
20
21
22
23

Figure 7-1: Installing the 472402A Backup Dialer

Do not run the ribbon cable underneath the backup dialer PC board.
The J6 header is static-sensitive. Make connections to the header with the power off, and after
grounding yourself.
The 472402A Dialer
Complies with FCC Rules, Part 68
FCC Reg. No.: AC398U-68628-MO-N
Ringer Equivalence: 0.7B
Connect to main PCB
header J6 using
BACK-UP
ribbon cable
PHONE JACK
(supplied)
(connect using supplied cable)
Supervision is programmable
BACK-UP DIALER EARTH GROUND SCREW
(wire to main PCB, terminal 3 or 4)
POINT 1
POINT 2
POINT 3
POINT 4
POINT 5 POINT 6
24
25
26
27
28
29
30
31
32
33
Section 7 – System Communication
RJ31X
MAIN
SERVICE
POINT 7 POINT 8
RJ31X
34
35
36
38
39
40
37
JACK
PHONE JACK
J5
1
2
3
4
5
6
7
8
9
MAIN
DIALER
LED
J6
1
2
3
4
5
6
7
8
9
7-3

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents