*80 Menu Mode: Defining Output Functions

Use this mode to program up to 48 output definitions that provide automated control of any of the 18
output devices, based on events ocurring on individual zones or zones with certain zone types. Each
output definition is identified by an output function number, and includes the following components:
Output Definition Components
Component
Output Function No.
Activated By
Event
Partition
Output Action
Output No.
For example, if you want to pulse a strobe light upon fire alarms on zone 4 using a relay mapped to
output number 2 (as programmed in *79 Menu Mode), program the following in *80 Menu Mode:
Prompt
Output Funct. # = 01 (assuming this is the first output function)
Activated By:
Enter Zn No.
Device Action
Device Number = 02 (device mapped in *79 Menu Mode)
Start Output Definition mode by pressing 80 while in Data Programming mode. The following
prompts are displayed:
∗80 Menu Mode
PROMPT
Output Funct. #
(00 = Quit)
01
01
A E P Trig
?00 0
0
– ZL=1
Description
A reference number from 01-48, which defines an output's characteristics.
Determines whether the initiating event occurs on a zone, a zone list, or a zone type.
Event that triggers the output action. Can be an event occurring on a specific zone
number or a zone list, or on the faulting of a specific zone type.
If the output is activated by zone type, this defines the partition in which the
programmed event is to cause the device action.
Defines the action of the relay/X-10 device when the defined event occurs. Can close for
2 seconds, stay closed until reset, continuously pulse (1-second close-open-close-open,
etc.), toggle the device state, or activate for a defined duration (set in data field *177).
Assigns this function to a specific output number (01-18). This is the output number
that will perform this function upon the triggering event. Note that each defined
function is associated with only one output number. This means that if more than one
output device needs to perform this particular function, you need to define another
output function number with the same attributes, but assign the appropriate output
number. (i.e. output devices can be assigned more than one function number, but each
function number can only be assigned a single output number.
Entry
= 3 (zone number)
= 04 (requires 2-digit zone numbers)
= 3 (continuos pulse)
VALID ENTRIES
Output Function No.
01-48
[ ∗ ] to continue
Summary Screen
[ ∗ ] to continue
EXPLANATION
Enter the Output function number 01–48 (or 00 to exit) to be defined.
This screen displays a summary of the current output programming
(for this example, Zone List has been selected-this is the default
screen).
A = Device Action; E = Triggering event; P = Partition; Trig =
Trigger type
NOTE: A question mark in the summary screen indicates that the
device number shown has not been mapped. Use *79 Menu mode to
map the device.