Figure 5-13: Loop Interface Module - ADT FOCUS 200 PLUS Installation And Setup Manual

Commercial fire and burglary security system with scheduling
Hide thumbs Also See for FOCUS 200 PLUS:
Table of Contents

Advertisement

FOCUS 200 PLUS Installation and Setup Guide
Mounting and Wiring the Loop Interface Module
To mount and wire the LIM, perform the following steps:
Step
1
2
3
4
5
5
6
7
5-22
TAMPER SWITCH
OPERATOR
248116 TAMPER SWITCH
(ORDERED SEPARATELY)
(NOTE 1)
SIM GATEWAY
TRUNK CONNECTIONS

Figure 5-13: Loop Interface Module

Action
Mount the housing unit in a location where the LIM will be protected from tampering or
damage caused by machinery-moving equipment.
Record the Hard ID number of the LIM and its associated gateway.
Snap the LIM circuit board into the housing.
Make the wiring connections from the LIM to the gateway (see Figure 5-13).
Make the wiring connections from the LIM to the sensor (see Figures 5-14 and 5-15). The
loop resistance must not exceed 300 ohms.
Using a 148380 Label (sensor number sheet), peel off the appropriate sensor point
number and stick it onto the cover of the housing unit. We recommend that a label
indicating the type of sensor involved and its location be affixed to the inside front cover
of the housing unit.
Close the cover of the housing unit.
Load the LIM point data into the control unit. See the Programming section for
information about the procedure.
TB2
TA
J1
1
2
3
4
5
6
1 (BLK)
2 (RED)
3 (YEL)
4 (BLU)
JUMPER J1
(REMOVE IF
USING TAMPER)
LOOP
CONNECTIONS
471943
HOUSING UNIT