Wiring The Hardwired Points - ADT FOCUS 200 PLUS Installation And Setup Manual

Commercial fire and burglary security system with scheduling
Hide thumbs Also See for FOCUS 200 PLUS:
Table of Contents

Advertisement

FOCUS 200 PLUS Installation and Setup Guide

Wiring the Hardwired Points

The wiring of the hardwired points is divided into four parts:
Wiring burglary and panic devices to points 1-8.
Wiring 2-wire smoke detectors to points 1 and 2.
Wiring 4-wire smoke detectors to points 1-8.
Wiring points 3 and 4 for style "D" configuration.
Wiring Burglary and Panic Devices to Points 1-8
To wire burglary and/or panic devices to points 1-8 (terminals 25 - 38), perform the following steps:
Step
1
2
The maximum loop resistance is 100 ohms for points 1 and 2, and 300 ohms for all other points (excluding
the 2K EOL resistor).
Wiring 2-Wire Smoke Detectors to Points 1 and 2
Points 1 and 2 have the added capability of supporting 2-wire smoke detectors. Each point provides
enough standby current (2mA) to power up to 16 of the smoke detectors listed below.
2K EOL resistors must be connected across the loop wires of each point at the last detector for fire
points.
The alarm current provided by points 1 and 2 will support only one smoke detector each in the alarmed
state.
Compatible 2-Wire Smoke Detectors
You may use up to 16 two-wire smoke detectors each on points 1 and 2 listed in the table below.
DETECTOR TYPE
Photoelectric, direct wire
Photoelectric w/heat sensor, direct wire
Photoelectric w/B401B base
Photoelectric w/heat sensor and B401B base
Ionization, direct wire
Ionization w/B401B base
Photoelectric duct detect. w/DH400 base
Photoelectric
Photoelectric duct detect. w/DH400 base
Ionization duct detector w/DH400 base
Ionization, direct wire
Ionization w/B110LP base
Photoelectric, direct wire
Photoelectric w/heat sensor, direct wire
Photoelectric w/B110LP base
Photoelectric w/Thermostat
4-2
Action
Connect normally closed devices in series with the high (+) side of the loop.
Note: The 2K EOL resistor must be connected in series with the devices, following the
last device.
Connect normally open devices in parallel (across) the loop.
Note: The 2K EOL resistor must be connected across the loop wires at the last device.
DEVICE MODEL #
System Sensor 2400
System Sensor 2400TH
System Sensor 2451
System Sensor 2451TH
System Sensor 1400
System Sensor 1451
System Sensor 2451
440354 (3534-2C)
System Sensor 2451
System Sensor 1451DH
System Sensor 1100
System Sensor 1151
System Sensor 2100
System Sensor 2100T
System Sensor 2151
435021 (3534-2CT)