5800 Series Transmitters; Figure 5-17: Rf Receiver Dip Switch Settings - ADT FOCUS 200 PLUS Installation And Setup Manual

Commercial fire and burglary security system with scheduling
Hide thumbs Also See for FOCUS 200 PLUS:
Table of Contents

Advertisement

FOCUS 200 PLUS Installation and Setup Guide
Mounting and Wiring the RF Receiver
To mount the RF receiver, perform the following steps:
Step
1
2
3
Addressing and Programming the RF Receiver
To address and program the RF receiver, perform the following steps:
Step
1
2

5800 Series Transmitters

5800 Series transmitters have built-in serial numbers (Hard ID) that must be programmed into the
system. The serial number may be programmed via the operating panel while programming the point
data, or via the downline loading.
For button-type transmitters (wireless keys), such as the 5804, 5802, and 5801, you must assign a
unique point number to each individual button used on the transmitter. Each button on the transmitter
also has a pre-designated loop or input number. Refer to the Programming section for a description of
the procedure for programming RF points.
If an RF transmitter is used to arm or disarm the system, the point must be linked to a user. Otherwise, the
system will show the arm/disarm prompts when the button is pressed, but the system will not change state.
5-26
Action
Remove the RF receiver's circuit board from its plastic case and mount the case, using
the appropriate mounting hardware. See receiver's instructions for mounting
information.
Note: The receiver can be mounted up to 500 feet from the RF gateway (see table below).
Wire gauge
Maximum length for one
receiver
#18
#22
Note: The length of all wire runs combined must not exceed 500 feet when unshielded
quad conductor cable is used (250 feet if shielded cable is used).
Connect the RF gateway to the RF receiver. See Figure 5-16 for wiring connections.
Install the two antennas into the right-hand terminals of the 2-terminal block in the
receiver (see receiver's instructions). If you are using a second receiver, install the
antennas on that receiver.
ON
OFF
*
DIP Switch Setting for
1st Receiver
(Address "1")

Figure 5-17: RF Receiver DIP Switch Settings

Action
Set the RF receiver's DIP switches as follows:
Set the first receiver's device address to "1" (see Figure 5-17). If a second receiver is used,
set its device address to "2."
Program the number of RF receivers via downline loading.
500 feet
225 feet
ON
OFF
SWITCH
*
*
POSITION 5
IS PRESENT
ONLY ON
5881EH (SEE
RECEIVER
INSTRUCTIONS
FOR USAGE)
DIP Switch Setting for
2nd Receiver
(Address "2")
Maximum length for two
receivers
250 feet
112 feet
-

Hide quick links: