Figure 5-1: Pid Gateway Module - ADT FOCUS 200 PLUS Installation And Setup Manual

Commercial fire and burglary security system with scheduling
Hide thumbs Also See for FOCUS 200 PLUS:
Table of Contents

Advertisement

FOCUS 200 PLUS Installation and Setup Guide
GATEWAY
MICROPROCESSOR
RS-485 BUS
ADDRESS JUMPERS
JUMPER E10
PID Gateway Applications
The PID Gateway is limited to applications involving the following items that cannot be used with the
SIM Gateway:
471898(7187-028) Quad Powered Sounder PID Module.
7187-039 Waterflow Retard Module.
471998(7187-112) Remote Keyswitch (requires 411997(7187-097) Switch Interface Module).
471999(7187-113) Janitor Keyswitch (requires 471997(7187-097) Switch Interface Module).
471921(7187-061) Daytime Annunciator.
Additionally, the following sensors must be connected to the PID gateway:
Lacing and foil.
4058 Type Glassbreak Detectors.
5-4
RS-485 BUS LEDs
TXD (YEL)
RXD (RED)
RS-485
DS1
DS2
TXD
RXD
E2
E3
E4
U6
E5
E6
E7
E8
E9
E 10
(BLU) 4
TRUNK 1A
(YEL) 3
(RED) 2
(BLK) 1
TB2
TERMINAL STRIP
TB2 FOR TRUNK 1A
0
1
E2
UNIT NO.
E3
E4
E5
E6
COMMUNICATION
E7
GROUP NO. 3
E8
E9
JUMPER IN
JUMPER CONDITIONING SHOWN FOR COMMUNICATION GROUP 3
IN COMBINATION WITH UNIT NUMBERS 0 THROUGH 7.
NOTES:
1. RS-485 BUS LEDs:
(A) TXD (YEL) FLASHES WHEN GATEWAY IS TRANSMITTING
(B) RXD (RED) FLASHES WHEN GATEWAY IS RECEIVING.
2. A 248116 TAMPER KIT MAY BE ORDERED SEPARATELY;
CONSISTS OF TAMPER SWITCH PLUS MOUNTING HARDWARE.
3. REMOVE JUMPERS E10 AND E11 UNLESS GATEWAY IS BEING
POWERED BY A SEPARATE POWER SUPPLY THAT IS RATED
AT MORE THAN 0.5A (SEE PHYSICAL DESCRIPTION).

Figure 5-1: PID Gateway Module

TERMINAL STRIP TB1
CONNECTIONS TO
RS-485 BUS
TB1
(BLK) 1
GND
(RED) 2
+ 12V
E1
(YEL) 3
COM
(BLU) 4
COM +
TRUNK 1B
TA
FOR TAMPER
(IF USED)
SEE NOTE 2
2
3
4
5
6
JUMPER OUT
JUMPER E1
(REMOVE JUMPER TO
DISCONNECT RS-485
TERMINATING RESISTOR)
JUMPER E11
E 11
1 (BLK)
2 (RED)
3 (YEL)
4 (BLU)
TB3
TERMINAL STRIP
TB3 FOR TRUNK 1B
7
UNIT NO.

Hide quick links: