Table 8: Diagnostics - Status Display For The Dali Network In The Wago-Dali Configurator And Solutions - WAGO 753-647 Manual

Dali multi-master module for wago-i/o-system 750
Hide thumbs Also See for 753-647:
Table of Contents

Advertisement

54
Diagnostics
The status for the following queries is displayed in the table entries:
Table 20: Diagnostics - Status display for the DALI network in the WAGO-DALI Configurator and
solutions
Table Columns
- Not available
NA
- Lamp is on
ON
- Device fault (error) Error or failure of device Check the failed device and replace it if
DF
- Lamp defect
LD
- Limit error
LE
- Duplicate address
DA
- Sensor in the active
AM
mode
Operating Hours
You can reset the logged operating hours in the last column of the table to 0 (e.g.,
for replacing a device).
You can replace single, defective devices easily and quickly. The WAGO-DALI
Configurator supports a "Replace" function for this. Using the [Restore] button,
the old short address of the previous device is assigned to the new device and the
device settings are then reconstructed using the data stored in the module
database.
Pos: 77 /Dokumentation allgemein/Gliederungselemente/---Seitenwechsel--- @ 3\mod_1221108045078_0.doc @ 21810 @ @ 1
Explanation
Device not available
The lamp is switched on
Lamp is defective
Violation of upper/lower
limit
Duplicate address
detected
Sensor is in the active
mode; sensor
transmitting data
Operating Hours
WAGO-I/O-SYSTEM 750
753-647 DALI Multi-Master Module
Solution
Check the device, the connection and
the address. If required, re-assign the
address for the device
(see Section "Addressing").
Status indication
defective. If required, perform data
import using the Replace function
([Restore] function)
(see Section "Configuration").
Replace the defective lamp.
Check the limit settings in the
configuration for the device concerned.
To delete duplicate addresses, select the
devices with the identical addresses and
then point to the function "Delete
selected duplicate addresses" in the
selection list on the right below the
table.
Then, click the button [Submit].
Status indication
Display of operating hours.
On a device replacement, for example,
you can reset the operating hours to 0.
To do this, select the corresponding
device and point to the function "Reset
selected operating hours" in the
selection list on the right below the
table.
Then, click the button [Submit].
Manual
Version 1.0.0

Hide quick links:

Advertisement

Chapters

Table of Contents
loading

Table of Contents