4.
Adjust the gap between the BUILDING EXHAUST DUCT and the DUCT from the
PROCESSOR to obtain the required static pressure.

MEASURING THE NEGATIVE STATIC PRESSURE:

!
Caution
Do not install the XML 300 if the pressure of the EXHAUST is not correct! Incorrect venting can
cause serious damage to the XML 300.
Duct Diameter
76 mm (3 in.)
102 mm (4 in.)
GAP
5. Connect the EXHAUST HOSE to the EXHAUST CONNECTION of the PROCESSOR.
8/1998
Negative Static Pressure, Water Head
MIN
0.76 mm (0.03 in.)
0.25 mm (0.01 in.)
BUILDING EXHAUST DUCT
figure 3 - 16
3-14
DUCT from the PROCESSOR
II 3058-4
MAX
1.02 mm (0.04 in.)
0.51 mm (0.02 in.)
KODAK AG Stuttgart