12.2
Fault messages can be read out via parameter
stored following a fault comprises the error group FXX (high-byte, hexadecimal) and
the code YY (low-byte, hexadecimal).
05/08
05/08
Error Messages
Code
F00
No fault has occurred.
00
Code
Frequency inverter overloaded.
F01
00
Frequency inverter overloaded (60 sec), check load behavior.
02
Short-term overload (1 sec), check motor and application parameters.
03
Code
F02
Heat sink temperature too high, check cooling and fan.
00
Temperature sensor defective or ambient temperature too low.
01
Code
F03
Inside temperature too high, check cooling and fan.
00
Inside temperature too low, check electrical cabinet heating.
01
Code
F04
Motor temperature too high or sensor defective, check connection
00
S6IND.
Motor circuit breaker tripped, check drive.
01
The V-belt monitoring reports no load on the drive.
02
03
Phase failure, check motor and wiring.
Code
F05
Overloaded, check load situation and ramps.
00
03
Short circuit or earth fault, check motor and wiring.
Overloaded, check load situation and current value limit controller.
04
Asymmetric motor current, check current and wiring.
05
Motor phase current too high, check motor and wiring.
06
Message from phase monitoring, check motor and wiring.
07
Modbus Instruction manual
Modbus Instruction manual
Current Error
General Fault Message
Meaning
Overload
Meaning
Heat Sink
Meaning
Inside
Meaning
Motor Connection
Meaning
Output Current
Meaning
260. The error code
81
81
Need help?