9.1.3 Control via Remote Contacts
In the operation mode Control via remote contacts (
quency inverter is addressed via parameter
The digital inputs S1IND ... S6IND and the multifunction input MFI1D of the frequency
inverter as well as inputs EM-S1IND ... EM-S3IND of the optional expansion modules
are emulated through Bit 0 ... Bit 9 of parameter
If the remote contacts are used, the inverter behaves in the same way as in the case
of addressing via the digital inputs. For the function and the parameterization of these
inputs, refer to the frequency inverter operating instructions.
Note:
Sequence in Statemachine:
The numbers indicated in the individual operating statuses (e.g. 0x23) signal the
corresponding feedback via the status word (bit 0...6).
Note:
Note:
60
60
A release is possible only if
bit 0 of the control word is set to "1" and
−
−
the release via hardware is set to "1"
Controller release via the software alone is not possible.
Power-On
Initialization
Switched On
0x23
Release
Release
On
Off
Operation
released
0x27
Inputs which are set via the control word can be monitored via the control
unit KP500 or the control software VPlus by means of parameter
tal Inputs
250.
Digital inputs are indicated as set only if the controller release signal is
present and if bit 0 in the control word is set to "1".
If data set change- over is used, make sure that the parameter
cal/Remote
412 is set to "2" (control via remote contacts) in all assigned
data sets.
Modbus Instruction manual
Modbus Instruction manual
Local/Remote
Control Word
410.
Control Word
Fault
Acknowledge
from any
412 = 2), the fre-
410.
Fault
0x08
status
Digi-
Lo-
05/08
05/08