The frequency inverter can be controlled via three different operation modes. These
operation modes set via parameter
Note:
Note:
For example, it is possible to control the frequency inverter via the serial interface and
to activate a local emergency operation mode if the controller fails. This switch-over is
also visible via the status word in bit "Remote".
The data set switch-over can be effected via control contacts at the digital inputs of
the frequency inverter or via the bus. For data set change-over via the bus, parameter
Data Set Selection
With the default setting
via the digital inputs.
If
the bus. At the same time, data set change-over via the digital inputs is deactivated.
Via parameter
This is independent of whether the data set change-over was done via the digital in-
puts or via
05/08
05/08
Local/Remote
412
Control via Con-
0 -
tacts
Control via State-
1 -
machine
Control via Remote
2 -
Contacts
1)
Statemachine is a standardized software module within the controller of
the frequency inverter. The Statemachine maps specified operating
statuses and the controller within the frequency inverter.
For operation via the serial interface, settings 0, 1 and 2 are relevant.
−
Further possible operation modes
the frequency inverter operating instructions. These relate to the con-
trol via the control unit KP500 and the control via digital signals.
−
Parameter
data set, you can switch over between the different operation modes.
414 is used.
Parameter
No.
Name/Meaning
414
Data Set Selection
Data Set Selection
Data Set Selection
414 is set to 1, 2, 3 or 4, the selected data set is activated via
Active Data Set
Data Set Selection
Modbus Instruction manual
Modbus Instruction manual
Local/Remote
412.
Supported Operation Modes
The Start and Stop commands as well as the direction of rota-
tion are controlled via digital signals.
The Start and Stop commands as well as the direction of rota-
tion are controlled via the DRIVECOM Statemachine
communication interface.
The Start and Stop commands as well as the direction of rota-
tion are controlled via virtual digital signals through the commu-
nication protocol.
Local/Remote
Local/Remote
412 is data set related, i.e. by selecting a
Min.
0
414 = 0, the data set change-over is done
249, the currently selected data set can be read out.
414.
1)
of the
412 are described in
Settings
Max.
Fact. Set.
4
0
49
49