Gas supply

Gas pipe sizing must consider the gas
input to this appliance, as well as other
gas appliances in the premises. The
gas supply termination is inside the
heater, and enters from the lower left
hand side of the appliance.
Once the gas connection is completed
and checked for gas leaks lock the
sliding plate in place to stop the
connection rattling, refer image below.
Purging the gas supply
Foreign materials and debris such as
swarf, filings etc. must be purged from
the gas supply. Failure to do so may
cause damage to the control valve
causing it to malfunction.
The use of rubber hose for any gas
connection to a fixed appliance is NOT
authorised by the manufacturer.

Room thermistor

Once installed the room temperature thermistor (supplied on a 1m cable) should be set so the
bulb on the end is outside of the fire box and into an area where room air will be drawn over it,
refer image above. Make sure it will still be accessible for service when the wall linings have been
installed.