Linear 1000 minimum framing dimensions (mm)
The framing dimensions have the studs offset. This is because the cavity needs to be
framed based on the centreline of the Linear glass, NOT the opening size.
IMPORTANT
Where there is a requirement for a symmetrical installation, the cavity size will need to
increase, refer diagram below.
945
Front face to
center of flue
Clearance (approx. 50 mm)
Shaded area denotes a clearance around the fire of approx. 50 mm.
On the RHS this is automatically achieved with the carry bar.
*
Minimum wallboard cutout, refer table on p.29
**
Maintain 25 mm clearance to combustibles for the first 500 mm of flue
•
All dimensions are assuming a 10 mm wallboard
•
Studs and joist are required directly below the support feet of the fire
•
Framing shown is 90 x 45 mm
•
Fire platform shown is 18 mm plywood
•
Allow room underneath the appliance for the gas supply to enter the fire cavity (min. 100 mm)
870
Glass centreline
1890 (for symmetrical cavity)
1565
945
1450
830
620
740
460
39 assumes
10 mm wallboard
Recommend that the lintel is left
until the fire is installed so min.
clearances can be maintained
403 mm assumes a 10 mm wallboard
on both sides of a double-sided unit.
415 mm is the min. for a single-sided
unit to maintain 50 mm clearance to
the back of the fire.
Linear installation guide 13563-H 08-19 | 15
403