Chapter 3: Configuring the Micro800 Expansion I/O 2085-IR8-SC Using CCW
High Byte
Process
Word
Alarm
Bits
Index
Latch
15
AO_0
CH
Ch 7:0
0
7
AO_00: Clear High/Low Process Alarm Latches
Bit
Name
Even
CL<n>
Odd
CH<n>
Section 3.6
Product Features
User's Manual Pub. 0300321-01 Rev. A
3.5.16 Output Bit Allocation
14
13
12
11
10
CL
CL
CH
CH
6
5
7
6
3.5.17 Output Bit Description
Description
Clear Low Process Alarm Latch
0: Normal Operation
1: Clear low process alarm latch
Clear High Process Alarm Latch
0: Normal Operation
1: Clear high process alarm latch
The following sections provide information on user-configurable parameters.
3.6.1 Data Format
The Data Format is used to define the display scale of the measured input data.
Each channel can display different formats, based on user-defined choices. This
module provides four options for channel input display:
Index
Data Format
0
Engineering Unit ×1
1
Engineering Unit ×10
2
Raw/Proportional
3
Percentage Full Scale
3.6.2 Input Type
The maximum range to display a measured input data in the input table is from -
32768 to +32767 as a signed 16-bit integer. The actual range is scaled to fit the
selected Input Type. For example, the valid range for Pt 385 types is from -200°C
to 850°C. In Engineering Unit ×1 format, the valid display range is from -2000 to
8500, which provides the resolution down to 1 decimal place.