3.6 Cables connection

3.6.1 Pay attention terms:

Danger: The battery system is high voltage DC system. Must make sure the grounding of the rack
is stable and reliable.
Danger: All the plugs and sockets of the power cables must be orange to orange and black to
black. Otherwise it will cause personal injury.
Danger: No short circuit or reserved connection of the battery system's anode and cathode.
Caution: Wrong communication cables connection will cause the battery system failure.
Grounding
The PowerCube-M1 modules' grounding is based on metal directly touch between
the module's surface and rack's surface. So it needn't grounding cables at all. If
uses normal rack, remove the paint at the corresponding place.
Rack Grounding:
If there is a grounding metal frame outside the rack, for example, the metal angle
steel frame at the bottom of the container, the fix hole of the fix frame can be fixed
directly with the metal frame of the container. Then through the grounding of the container to
ensure reliable grounding.
If want to connect the ground cable, it can be connected to the M8 grounding bolt on the
frame base. Grounding cable must blAWG.
Grounding Bolt
3.6.2 Cables Connection
Note: Power cable uses water-proofed connectors. It must keep pressing this
Lock Button during pulling out the power plug.
11 / 32
Fix Hole
× 4