Annex 3: System Turn Off Progress List - Pylontech PowerCube-M1 Operation Manual

Lithium-ion phosphate energy storage system
Hide thumbs Also See for PowerCube-M1:
Table of Contents

Advertisement

Annex 3: System Turn OFF Progress List

Tick after
No.
completion
1
2
3
4
5
Turn off the switch between PCS and this battery string
(PowerCube-M1), or turn off the power switch of PCS, to
make sure no current through this battery string.
Turn off the "Power Output Switch" of the BMS.
Turn off the "Power Switch" of the BMS.
Turn off the "Power Switch" of the MBMS.
Turn off the UPS.
The UPS can turn on to check the equipment (PCS
or battery system etc.). Otherwise must turn off the
UPS to save its power.
32 / 32
Item
Remark
Refer to chapter
3.6.5.
Refer to chapter
3.6.5.
Refer to chapter
3.6.5.
Refer to chapter
3.6.5.
Refer to chapter
3.6.5.
19PIMV0802