Control Module (Bms) And All Battery Modules Install Into The Rack; Install The Mbms Into A 19' Standard Rack [On The Top Of Bms, Or Use The Rack Configured By User]; Cables Connection; Grounding Connection - Pylontech PowerCube-X1 Operation Manual

Lithium-ion phosphate energy storage system
Hide thumbs Also See for PowerCube-X1:
Table of Contents

Advertisement

3.5.4 Control Module (BMS) and all Battery Modules install into the Rack

Install the buckle nuts. The position of nuts must meet the position of the control module (BMS)
l
and all battery modules.
Install the control module (BMS) and all battery modules in. Each module uses 4 screws to fix.
l
3.5.5 Install the MBMS into a 19' standard rack [On the top of BMS, or use the rack configured
by user]
Install the buckle nuts. The position of nuts must meet the position of the MBMS.
l
Install the MBMS in. Uses 4 screws to fix.
l

3.6 Cables connection

3.6.1 Grounding connection:

Danger: The battery system is high voltage DC system. Must make sure the grounding of the rack
is stable and reliable.
Danger: All the plugs and sockets of the power cables must be orange to orange and black to
black. Otherwise it will cause personal injury.
Danger: Isolation breakers or switches for each battery string must be installed for maintenance.
Danger: No short circuit or reserved connection of the battery system's anode and cathode.
EU20PIXV0501
20 / 38