The both side of BMS to MBMS communication cable must be marked with labels.
The last port of Ethernet Switch is for the MBMS.
From the 1
port to the n
st
can fastest find out the corresponding battery string on the Ethernet Switch.

3.6.3 ADD Switch Setting (Address Assignment)

ADD Switch is a 6 bit dial switches to manually distribute the
communication address of the battery system. Nether position is OFF,
means "0". Upper position is ON, means "1". 1
address, and the 6
bit dial switch support a 120Ω resistance (Terminal
th
Resistance).
ADD Switch MBMS is a 6 bit dial switches to manually distribute the
communication address of the battery system. Nether position is OFF,
means "0". Upper position is ON, means "1". 1st bit to 4th bit is for
address, the 5th and the 6th bit dial switch support a 120Ω resistance
(Terminal Resistance).

3.6.3.1 Under communication for single BMS (battery string qty. 1 set)

The BMS's first five bits must set in below <BMS's Address Configure Table>. The last BMS's terminal
resistance must set in "1" (X=1);
The address is configured follow ASCII code: ("X" is terminal resistance).
BMS's Address Configure Table:
C A N
M odbus
A ddress di al bi t
0
1
00000X
1
1
10000X
2
2
01000X
3
3
11000X
4
4
00100X
5
5
10100X
6
6
01100X
3.6.3.2 Under CAN Communication Mode between MBMS and BMS (battery string qty. s6 set)
The BMS's first five bits must set in below <BMS's Address Configure
Table>. The last BMS's terminal resistance must set in "1" (X=1), and
other BMS's terminal resistance must set in "0".
The address is configured follow ASCII code: ("X" is terminal
resistance).
BMS's Address Configure Table:
The MBMS's ADD Switch set with "000011". The last 2 bits are terminal
resistances.
Note: the 1
to 4
bit dial for MBMS refer to 3.6.3.4.
st
th
3.6.3.3 Under Ethernet communication between MBMS and BMS (battery
port are for the corresponding battery string (PowerCube-M1). So we
th
14 / 32
bit to 5
bit is for
st
th
Battery
Battery
Address Bit
String
String
1
10000X
9
2
01000X
10
3
11000X
11
4
00100X
12
5
10100X
13
6
01100X
14
7
11100X
15
8
00010X
16
19PIMV0802
Addre
10
01
11
00
10
01
11
00

Advertisement