5.7. Installation location

- The heat pump has to be installed in
a frost-proof room! (room temperature
- In order to minimize oscillations and sounds
within buildings, heat pumps should be decou-
pled as far as possible from the building mass.
It is principally recommended to avoid installing
be omitted around the heat pump.
- The installation in wet or damp environments or
in areas exposed to dust or explosion hazards is
non-permissible.
- If refrigerant escapes from the installation site,
this must not enter adjacent rooms, stairways,
yards, corridors or drainage systems and a
hazard-free drainage must be ensured.
- In the case of danger, leave the installation site
immediately.
- If the size of the installation site falls below the
requested minimum size, this has to be designed
as machinery room in compliance with EN 378.
-
mechanical ventilation must be provided. A
mechanical ventilation shall be installed with
an independent emergency control beyond the
installation site and near the door to that area.
- Heat pumps must not be installed in rooms with
- Air intakes and outlets have to be safeguarded
against theft by appropriate on-site measures.
(C) IDM Energiesysteme GmbH

5.8. Space requirements and accessibility

In order to guarantee maintenance and operation of
the heat pump, a minimum distance of 800 mm has
to be observed on the front side (for operation and
maintenance).
By observing this distance an unobstructed system
maintenance and operation can be guaranteed.
Heating connections /
Electrical connections
Installation instructions AERO ILM
Opposite the outlet opening in the heat
pump the pre-installed condensate
condensate. For this purpose a drain-
age must be provided.