5.12.3.
Air inlet side
Procedure as in corner installation
Outlet panel:
The outlet panel is mounted to the desired side using
the 4 screws included in the delivery contents.
Example of outlet side on the right
A trapeze-shaped insulation with adhesive tape on
both sides is included with the outlet panel. This has
opening using suitable assembly material. Four bore
purpose!
Flexible hose:
The hose can be cut to length as desired! In connect-
is telescoped at the two ends.
(C) IDM Energiesysteme GmbH
clamp. This enables the insulation to be extended
directions. The minimum bending radius is 600 mm!!
with an assembly tape (perforated tape)!
Installation instructions AERO ILM
The air hose should be straight as far as
possible and should not make any un-
necessary changes in direction . The air
hose should be suspended every 0.5 m
The heat pump must only be moved us-
ing the mounted panels!
Installation
39