Installation Location; Space Requirements And Accessibility - iDM AERO ILM 2-7 Installation Instructions Manual

Modulation air-water-heat pumps for indoor installation
Table of Contents

Advertisement

5.7. Installation location

- The heat pump has to be installed in
a frost-proof room! (room temperature
must lie between 5 °C and 25°C!)
- In order to minimize oscillations and sounds
within buildings, heat pumps should be decou-
pled as far as possible from the building mass.
It is principally recommended to avoid installing
heat pumps on ceilings and fl oors in lightweight
construction. In the case of fl oating fl oor screed,
fl oor screed and impact sound insulation should
be omitted around the heat pump.
- The installation in wet or damp environments or
in areas exposed to dust or explosion hazards is
non-permissible.
- If refrigerant escapes from the installation site,
this must not enter adjacent rooms, stairways,
yards, corridors or drainage systems and a
hazard-free drainage must be ensured.
- In the case of danger, leave the installation site
immediately.
- If the size of the installation site falls below the
requested minimum size, this has to be designed
as machinery room in compliance with EN 378.
- If the emergency ventilation is not suffi cient,
mechanical ventilation must be provided. A
mechanical ventilation shall be installed with
an independent emergency control beyond the
installation site and near the door to that area.
- Heat pumps must not be installed in rooms with
high EMC load!
- Air intakes and outlets have to be safeguarded
against theft by appropriate on-site measures.
(C) IDM Energiesysteme GmbH

5.8. Space requirements and accessibility

In order to guarantee maintenance and operation of
the heat pump, a minimum distance of 800 mm has
to be observed on the front side (for operation and
maintenance).
By observing this distance an unobstructed system
maintenance and operation can be guaranteed.
Heating connections /
Condensation run-off /
Electrical connections
min. 800 mm
Installation instructions AERO ILM
Opposite the outlet opening in the heat
pump the pre-installed condensate
hose must be positioned to drain off
condensate. For this purpose a drain-
age must be provided.
Installation
25

Advertisement

Table of Contents
loading

This manual is also suitable for:

Aero ilm 4-13Aero ilm hgl

Table of Contents