Dimensioning - iDM AERO ILM 2-7 Technical Documentation Installation Instructions

Modulation air-water-heat pumps for indoor installation, with navigator 2.0 control
Hide thumbs Also See for AERO ILM 2-7:
Table of Contents

Advertisement

3. Dimensioning

3. General description
Dimensioning
An air/water-heat pump should be dimensioned in
such a way that the bivalence point lies between -3
the annual heating requirement (Austria, Germany,
Switzerland) will be covered by the heat pump.
In dimensioning the system the maximum heating
output of the house including the water for domestic
use is calculated.
The standard outside temperature is additionally re-
quired. This is determined by the geographical loca-
tion and can be found on the IDM homepage and ob-
tained from various institutions.
Heating energy required:
Heating performance diagram AERO ILM 4-13
16
required heating capacity at
standard external temperature
Bivalence
incl. domestic hot water required
part
14
{
12
10
8
6
4
2
0
-20
-15
standard external temperature
10
domestic hot water required
-10
-5
outside temperature [°C]
Installation instructions AERO ILM
Example:
Detached single-family house in Germany
4 person-household
Heating output requirements
Standard outside temperature
W35 EN14
W35 EN14511
W35 EN14511
bivalence point of the
particular heatpump type
0
5
11 kW
MAX
NOMINAL
MIN
10
15
heating limit
(C) IDM ENERGIESYSTEME GMBH
20

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Aero ilm 4-13

Table of Contents