iDM TERRA AL 60 Max Technical Documentation Installation Instructions

iDM TERRA AL 60 Max Technical Documentation Installation Instructions

Air-water-heat pumps for outdoor installation with navigator 2.0 controler
Table of Contents

Advertisement

T E C H N I C A L D O C U M E N TAT I O N
I N S TA L L AT I O N I N S T R U C T I O N S
DIE ENERGIEFAMILIE
T E R R A A L 6 0 M a x
wi t h N AV I GATO R 2.0 C o n t ro l e r
Air-water-heat pumps
for outdoor installation
HEAT PUMPS FROM AUSTRIA
www.idm-energie.at

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the TERRA AL 60 Max and is the answer not in the manual?

Questions and answers

Summary of Contents for iDM TERRA AL 60 Max

  • Page 1 DIE ENERGIEFAMILIE T E R R A A L 6 0 M a x wi t h N AV I GATO R 2.0 C o n t ro l e r Air-water-heat pumps for outdoor installation HEAT PUMPS FROM AUSTRIA www.idm-energie.at...
  • Page 2: Table Of Contents

    1.15. Intended use 1.16. Scope of delivery 1.17. Accessories 2. T ECHNICAL DATA 2.1. Dimensions TERRA AL 60 Max 2.2. Dimensions electrical cabinet 2.3. Technical data 3. D IMENSIONING 3.1. Heat output at different fl ow temperatures and full power (2-stages) 3.2.
  • Page 3 5.7. TERRA AL 60 Max with heating and cooling buffer 5.8. TERRA AL 60 Max cascade system with heating buffer 5.9. TERRA AL 60 Max cascade system with Hygienik without layer seperate plate and heating buffer 6. E LECTRICAL CONNECTION 6.1.
  • Page 4: General Description

    We recommend you to sign manually. The transport fi xtures must not be used for a maintenance contract with your competent cus- transporting the components with a crane or similar tomer service. hoisting equipment. (C) IDM ENERGIESYSTEME GMBH Installation instructions TERRA AL 60 Max...
  • Page 5: Cleaning

    Water piping must be de- to a condensation on the cabinet of the signed frost-proof. outdoor unit. (C) IDM ENERGIESYSTEME GMBH Installation instructions TERRA AL 60 Max...
  • Page 6: Information On Environmental Protection

    6 heating circles can be con- manual must be observed. trolled. The TERRA AL 60 Max is fi lled with the safety refrig- These comprise among others: erant R410A. The NAVIGATOR control includes an internal heat metering. This means there are no lon- - the generally valid accident prevention and safety ger additional fl...
  • Page 7: Intended Use

    (e.g. underfl oor heating, wall heating, low-tempera- ture radiator heating ...). TERRA AL 60 Max heat pumps function with the safe- ty refrigerant R410A which, if in the event of a proper assembly and installation circulates in a closed cir- cuit, represents practically no environmental impact.
  • Page 8: Technical Data

    2. General description 2. Technical data Technical data 2.1. Dimensions TERRA AL 60 Max side view front view (air outlet) 3270 rear view (air inlet) Dimensions HxWxD [mm] 1500x3270x920 weigth [kg] refrigerant side [kg] evaporator side [kg] 310 kg 570 kg 2.2.
  • Page 9: Technical Data

    Sound power level (part load) dB(A) Noise-reduced operation full load dB(A) The sound pressure level can be calculated with the iDM-sound calculation tool Uncertainty of measurement ± 1,5 dB(A) (C) IDM ENERGIESYSTEME GMBH Installation instructions TERRA AL 60 Max...
  • Page 10 C/K 63 Fuse control supply B/Z 13 Fuse heating element up to 9 kW (on site) B/Z 13 Prodection class outdoor unit IP 44 Prodection class indoor unit IP 20 (C) IDM ENERGIESYSTEME GMBH Installation instructions TERRA AL 60 Max...
  • Page 11: Dimensioning

    3.1. Heat output at different fl ow temperatures and full power (2-stages) ß outdoor temperature [°C] 3.2. Heat output at different fl ow temperatures and partial load (1-stage) outdoor temperature [°C] (C) IDM ENERGIESYSTEME GMBH Installation instructions TERRA AL 60 Max...
  • Page 12: Limitation Of Use - Heating

    If the outside temperatures are below or above of the application range, the heat pump switches off . If a bivalence exists and is confi gured in the navigator, bivalence mode will start. (C) IDM ENERGIESYSTEME GMBH Installation instructions TERRA AL 60 Max...
  • Page 13: Placement And Installation

    4.1. Installation instructions Inlet air: The inlet air must be free of impurities such as sand The TERRA AL 60 Max is only designed for exterior and caustic materials such as ammonia, sulphur, installation. Special actions has to be set for frost chlorine, etc.
  • Page 14: Acoustic Evaluation

    • refl ection on acoustically hard ground e.g. glass facade and stone surfaces • attenuation due to sound absorbing porous sur- faces e.g. grass, trees • reinforcement/reduction of by wind speed/direction (C) IDM Energiesysteme GmbH Installation instructions TERRA AL 60 Max...
  • Page 15 • The airfl ow should not be blown directly against information incorporation 0.3 or 6 dB walls as sound refl ections lead to increased sound impulsiveness 0.3 or 6 dB pressure levels accordingly. daytimes with increased 6 dB sensitivity (C) IDM Energiesysteme GmbH Installation instructions TERRA AL 60 Max...
  • Page 16: Transport

    When the heat pump is located on its fi nal site, the crate may be removed. During transport pay attention to the focus! On the heatpump you fi nd stickers marking the focus. focus (C) IDM Energiesysteme GmbH Installation instructions TERRA AL 60 Max...
  • Page 17: Placing The Heat-Pump On Site

    When the heat pump is loacated on its fi nal site, the crate can be removed. The standing feet are turned up- wards, and the pallet is removed. Subsequently, the heat pump must be leveled. The heat pump must be leveled by the 4 base feet (100 mm). (C) IDM Energiesysteme GmbH Installation instructions TERRA AL 60 Max...
  • Page 18: Foundation Construction

    2 x condensate run off height adjustable base feet (4 pcs.) The condensation run off and the hydraulic and electric connections are located on the rear (air inlet) of the heat pump. (C) IDM Energiesysteme GmbH Installation instructions TERRA AL 60 Max...
  • Page 19 2860 3260 The ground must be a fi rm and level surface. It is possible to install concrete bases or other good bearing components. The load capacity must be guaranteed. (C) IDM Energiesysteme GmbH Installation instructions TERRA AL 60 Max...
  • Page 20: Wind Direction

    1000 mm min. 800 mm heating side and electri- cal connections 3270 mm condensation outlet The minimum distances must be respected, because of the case of maintainance and to prevent air-short-circuits. (C) IDM Energiesysteme GmbH Installation instructions TERRA AL 60 Max...
  • Page 21: Space Requirements Cascade

    800 mm min. 800 mm min. 1000 mm min. 2000 mm Side by side it is possible to cascade up to 5 TERRA AL 60 Max heat pumps. Example 2 Top view min. 800 mm min. 800 mm min. 1000 mm min.
  • Page 22: Condensate Run Off

    The heating cable must not be laid in loops, and only as a single cable. The heating cable must not touch itself (grinding - minimum distance 50 mm). Smallest bending radius 25 mm. (C) IDM Energiesysteme GmbH Installation instructions TERRA AL 60 Max...
  • Page 23: Heating Connections

    Incorrect fl ow volumes due to incorrect pipework, false fi xtures or improper pump operation can cause damage! The hydraulic executions must be expertly insulated (heat loss and noise reduction) (C) IDM Energiesysteme GmbH Installation instructions TERRA AL 60 Max...
  • Page 24: Frost Protection

    TERRA AL Buffer M73-1 B14 M73-2 Basic scheme, only neccessary if an additional safety brine circuit is provided. (C) IDM Energiesysteme GmbH Installation instructions TERRA AL 60 Max...
  • Page 25: Cleaning Fi Lter Ball Valve

    The heat pump fl ow is connected at a height of around 1.150 mm and the heat pump return at a height of around 620 mm. Details without fl exible connection hoses. (C) IDM Energiesysteme GmbH Installation instructions TERRA AL 60 Max...
  • Page 26: Terra Al 60 Max With Heating Buffer And Mixed Heating Circles

    5. General description Heating connections 5.5. TERRA AL 60 Max with heating buff er and mixed heating circles (C) IDM Energiesysteme GmbH Installation instructions TERRA AL 60 Max...
  • Page 27: Terra Al 60 Max With Hygienik Without Layer Seperate Plate And Heating Buffer

    Heating connections 5.6. TERRA AL 60 Max with Hygienik without layer seperate plate and heating buff er (C) IDM Energiesysteme GmbH Installation instructions TERRA AL 60 Max...
  • Page 28: Terra Al 60 Max With Heating And Cooling Buffer

    5. General description Heating connections 5.7. TERRA AL 60 Max with heating and cooling buff er (C) IDM Energiesysteme GmbH Installation instructions TERRA AL 60 Max...
  • Page 29: Terra Al 60 Max Cascade System With Heating Buffer

    Heating connections 5.8. TERRA AL 60 Max cascade system with heating buff er (C) IDM Energiesysteme GmbH Installation instructions TERRA AL 60 Max...
  • Page 30: Terra Al 60 Max Cascade System With Hygienik Without Layer Seperate Plate And Heating Buffer

    5. General description Heating connections 5.9. TERRA AL 60 Max cascade system with Hygienik without layer seperate plate and heating buff er (C) IDM Energiesysteme GmbH Installation instructions TERRA AL 60 Max...
  • Page 31: Electrical Connection

    Type „B“ or „Z“ are suffi cient. required. The connection to the protective measure „protective multiple earthing“ is suffi cient. If never- The TERRA AL 60 Max is equipped with two starting theless the protective measure „fault-current circuit current limiter.
  • Page 32: Connection Diagram For The Electric Components

    113 114 115 116 117 118 119 120 121 122 123 Extension module external / Cascade participant EEV2 X4 EEV1 X2 RS232 X36 LAN X33 132 131 130 - SH Touchdisplay Extension module internal (C) IDM Energiesysteme GmbH Installation instructions TERRA AL 60 Max...
  • Page 33: Emc Compatibility

    - Short-term measurement errors - Long-term measurement errors - Short-term interruption of data connections Lightning protection and - Long-term interruption of data connections potential compensation - Data loss - Damage to the equipment (C) IDM Energiesysteme GmbH Installation instructions TERRA AL 60 Max...
  • Page 34: Assigning The Inputs On The Central Unit

    In the case of maintenance operations, ensure that The sensors have to be set as shown on the piping the potential equalization is restored properly once schemes. the maintenance has been fi nished. (C) IDM Energiesysteme GmbH Installation instructions TERRA AL 60 Max...
  • Page 35: Maximum Delimitation In Underfl Oor Heating

    Room thermostat Room 1 Room 2 Room 3 Zone valve with end switch Zone 1 Zone 2 Zone 3 Navigator main board Room engine heating circuit A (C) IDM Energiesysteme GmbH Installation instructions TERRA AL 60 Max...
  • Page 36: Start-Up

    After pressing the main switch on the heat pump, the start-up assistant is started after selecting the desired If an error occurs several times in sequence, language. please contact your iDM customer service! Customer service phone No.:____________________ (C) IDM Energiesysteme GmbH Installation instructions TERRA AL 60 Max...
  • Page 37: Performance Data According En 14511

    8. Appendix Appendix 8.1. Performance data according EN 14511 (C) IDM Energiesysteme GmbH Installation instructions TERRA AL 60 Max...
  • Page 38: Product Data Sheet - Energy Label

    Product data sheet In addition to the supplementing Directive (EU) Nr: 811/2013 in line with Commission Delegated Regulation 2010/30 EU Energy labelling Manufacturer: IDM Energiesysteme, Seblas 16 18, 9971 Matrei in Osttirol Heat pump type TERRA AL 60 Max Heat transfer media...
  • Page 39: Declaration Of Conformity

    Appendix 8.3. Declaration of Conformity (C) IDM Energiesysteme GmbH Installation instructions TERRA AL 60 Max...