Aero Ilm 4-13 - Performance Data Heating - Detailed - iDM AERO ILM 2-7 Technical Documentation Installation Instructions

Modulation air-water-heat pumps for indoor installation, with navigator 2.0 control
Hide thumbs Also See for AERO ILM 2-7:
Table of Contents

Advertisement

9. General description
Appendix

9.3. AERO ILM 4-13 - Performance data heating - detailed

Flow temperature 35 °C
heat capacity [kW]
power consumption [kW]
COP
heat capacity [kW]
power consumption [kW]
COP
heat capacity [kW]
power consumption [kW]
COP
Flow temperature 45 °C
heat capacity [kW]
power consumption [kW]
COP
heat capacity [kW]
power consumption [kW]
COP
heat capacity [kW]
power consumption [kW]
COP
Flow temperature 55 °C
heat capacity [kW]
power consumption [kW]
COP
heat capacity [kW]
power consumption [kW]
COP
heat capacity [kW]
power consumption [kW]
COP
Flow temperature 60 °C
heat capacity [kW]
power consumption [kW]
COP
heat capacity [kW]
power consumption [kW]
COP
heat capacity [kW]
power consumption [kW]
COP
66
20
15
12
15,20
15,43
15,20
3,44
3,67
3,81
4,42
4,20
3,99
9,90
9,59
9,15
1,69
1,76
1,77
5,86
5,45
5,17
5,58
5,75
5,08
0,83
0,84
0,85
6,72
6,85
5,98
20
15
12
14,31
14,18
14,14
3,81
4,11
4,37
3,76
3,45
3,24
9,32
8,81
8,51
1,87
1,97
2,03
4,98
4,47
4,19
5,25
5,28
4,72
0,92
0,94
0,97
5,72
5,62
4,85
20
15
12
13,43
13,18
13,06
4,74
4,94
5,14
2,83
2,67
2,54
8,75
8,19
7,86
2,33
2,37
2,39
3,76
3,46
3,29
4,93
4,91
4,36
1,14
1,13
1,15
4,31
4,35
3,80
20
15
12
13,07
12,73
12,54
5,33
5,52
5,73
2,45
2,31
2,19
8,51
7,91
7,55
2,62
2,65
2,66
3,25
2,99
2,84
4,80
4,74
4,19
1,29
1,26
1,28
3,73
3,76
3,28
Installation instructions AERO ILM
outdoor temperature [°C]
10
7
2
15,10
14,50
12,67
3,89
3,94
3,99
3,88
3,68
3,18
8,90
8,28
7,11
1,79
1,74
1,73
4,97
4,76
4,11
4,80
4,35
3,76
0,84
0,82
0,82
5,71
5,30
4,58
outdoor temperature [°C]
10
7
2
14,01
13,55
11,93
4,48
4,62
4,52
3,13
2,93
2,64
8,26
7,74
6,69
2,06
2,04
1,96
4,01
3,79
3,41
4,45
4,06
3,54
0,97
0,96
0,93
4,61
4,23
3,81
outdoor temperature [°C]
10
7
2
12,96
12,60
11,14
5,28
5,57
5,63
2,45
2,26
1,98
7,64
7,20
6,25
2,43
2,46
2,44
3,14
2,93
2,56
4,12
3,78
3,30
1,14
1,16
1,16
3,61
3,26
2,86
outdoor temperature [°C]
10
7
2
12,40
11,90
10,64
5,87
6,07
6,23
2,11
1,96
1,71
7,31
6,80
5,97
2,70
2,68
2,70
2,71
2,54
2,21
3,94
3,57
3,15
1,27
1,26
1,28
3,11
2,83
2,47
-7
-10
-15
10,90
10,17
8,94
4,15
4,19
4,26
2,63
2,43
2,10
5,50
4,97
4,08
1,68
1,68
1,69
3,27
2,96
2,42
2,85
2,86
2,88
0,80
0,93
1,15
3,57
3,08
2,50
-7
-10
-15
9,71
9,19
8,33
4,62
4,61
4,56
2,10
1,99
1,83
4,90
4,49
3,81
1,87
1,85
1,81
2,62
2,43
2,10
2,54
2,58
2,68
0,89
1,02
1,23
2,86
2,52
2,18
-7
-10
-15
9,06
8,21
-
6,00
6,06
-
-
1,51
1,35
4,57
4,01
-
2,43
2,43
-
-
1,88
1,65
2,37
2,31
-
1,16
1,35
-
2,05
1,72
-
-7
-10
-15
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
(C) IDM Energiesysteme GmbH
-18
8,17
4,27
1,91
3,58
1,74
2,06
2,83
1,34
2,11
-18
7,39
4,37
1,69
3,24
1,78
1,82
2,56
1,37
1,87
-18
-
-
-
-
-
-
-
-
-
-18
-
-
-
-
-
-
-
-
-

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Aero ilm 4-13

Table of Contents