Corner Installation - iDM AERO ILM 2-7 Technical Documentation Installation Instructions

Modulation air-water-heat pumps for indoor installation, with navigator 2.0 control
Hide thumbs Also See for AERO ILM 2-7:
Table of Contents

Advertisement

5. General description
Installation

5.9. Corner installation

Optimum results are achieved if the heat pump is installed in a corner! The wall openings can be implemented
by the building contractor. The wall openings must be insulated with closed porous insulating material (density
50 mm).
5.9.1. Preparation on the construction side - clearance dimensions
Adjustable feet under the heat pump are provided for this purpose.
Outlet opening to the right
NOTE: Clear dimensions. Increase
the Wall opening according the
insulation.
around the wall insulation.
To facilitate accessibility the outlet opening on the right-hand side should be given preference!
When using a light shaft this must be at least as wide as the wall opening. The depth must be at
least 400 mm.
26
Installation instructions AERO ILM
Outlet opening to the left
NOTE: Clear dimensions. Increase
the Wall opening according the
insulation.
(C) IDM Energiesysteme GmbH