The COMBIVERT R6 is conditionally short-circuit proof (EN 61800-5-1 /
VDE 0160). The intended function is guaranteed after resetting the internal
protection devices.
Condition-
ally short-
Exception:
circuit proof
If earth- or short-circuits often occurs at the output, this can lead to a defect
(regenera-
in the unit.
tion)
With applications requiring the COMBIVERT R6 to be switched on and off cycli-
cally, maintain an off-time of at least 5 min. If you require shorter cycle times
Cyclic acti-
please contact KEB.Switching off during the initialization phase can cause un-
vation and
defined conditions.
deactiva-
tion
When using systems with RCD, the instructions or the requirements of VDE
RCD (resid-
0100 -T 530 (IEC 60364-5) must be observed. The recommended tripping cur-
ual current
rent of RCD type "B" is 300 mA.
operated
circuit-
breaker)