Installation

6.
Installation
6.1

EMC-compatible control cabinet installation

1
Mains fuse
2
Main contactor
3
HF-side-mounted filter (≥ size 25
R-S or R6-N)
HF-sub-mounted filter (≤ size 19
R6-S)
4
if necessary external synchroniza-
tion
5
Commutation reactor / harmonic
filter
6
COMBIVERT R6
7
if necessary external DC fuses
8
Frequency inverter
9
Motor lines
10
Protective Earth (PE) on the
A
mounting plate power circuit
10b Protective Earth (PE) on the
mounting plate control circuit
10c
Equipotential bonding with the
housing earth
11
Mains connection power circuit
11 A Mains connection control circuit
12
Control lines
Large area contact at the mounting
plate
Figure 26:
6.2

Installation instructions

• Stationarily install and earth COMBIVERT.
• The device must not be permeated by mist or water.
• Allow for sufficient heat dissipation if installed in a dust-proof housing.
• Install the COMBIVERT in an appropriate housing in accordance with the local
• Protect COMBIVERT against conductive and aggressive gases and liquids.
• The lines of the R6-S commutation reactor must be limiting to 50 cm.
• The frequency inverters must be placed in the immediate vicinity of the R6-S.
GB - 74
EMC-compatible control cabinet installation
regulations when operating it in explosion-endangered spaces.
12
150 mm
3
2
1
5
11a
11
10a
Control circuit
Power circuit
150 mm
6
4
150 mm
150 mm
7
10b
10c
Direction of the
cooling fins
8
30 mm
9a
9b