6.3.2
Connection terminals of the power circuit
All terminal strips meet the requirements on EN 60947-7-1 (IEC 60947-7-1)
View of power supply and regenerative units
The terminals of a power supply and regenerative unit can be input or output
dependent on the actual operating status (power supply or regeneration). For the
standardization of the view the line side is always regarded as input and the DC
voltage side is always regarded as output.
L1.2
L2.2
L3.2
Terminals
++, – –
L1.2, L2.2, L3.2 Mains input 3-phase coming from the commutation reactor
Figure 28:
R6-S in E housing
Description of terminals at KEB inverters
DC voltage output with starting current limiting for loading the connected
inverter; usable as input for regenerative operation. If inverters with mains
supply of type A1 or A2 (see 4.3.1) are available in the DC bus, these may
be switched to mains only after loading the DC bus. Note the maximum
DC link capacity or decoupling diodes !
Description of the input terminals of the COMBIVERT R6
Connection of the COMBIVERT R6
R6-S in R and P housing without internal
++
L1
I_LSF
+
L2
--
DC fuses
L1.2
+
L2.2
L3.2
++
--