No.
Name
CP.08

DC current

Resolution
0.1 A
No.
Name
CP.09

DC voltage

Resolution
1 V
No.
Name
CP.10

peak DC voltage

Value range
0...1000 V
No.
Name
CP.11

power module temperature

Resolution
1 °C
No.
Name
CP.12

OL counter display

Resolution
1 %
Monitoring and analysis parameters
Meaning
Display of the calculated DC output current in ampere.
Meaning
Display of actual DC link voltage in volt. The value is measured at the
DC output terminals of the COMBIVERT R6-S.
Meaning
Parameter CP.10 enables to recognize voltage peaks within an operat-
ing cycle. For that the highest value of CP.09 is stored in CP.10. The
peak value memory can be cleared by pressing the UP and DOWN
key or over bus by writing any value you like to the address of CP.10.
Switching off COMBIVERT R6-S also clears the memory.
Meaning
Display of the actual power module temperature. On exceeding the
maximum power module temperature (see "technical data") the modu-
lation is switched off and error E.OH is displayed. Message E.nOH is
displayed after the cooling period. The error can be reset now.
Meaning
The permanent load of the COMBIVERT R6-S can be evaluated with
this parameter, in order to avoid an E.OL error (in-time load reduction).
Error E.OL is released, if the overload counter reaches 100 %.
r/w
Enter
Origin
ru.15
r/w
Enter
Origin
ru.19
r/w
Enter
Origin
ru.20
r/w
Enter
Origin
ru.38
r/w
Enter
Origin
ru.39
GB - 95