Connection of the COMBIVERT R6
All terminals must be provided with
cover caps against electric shock.
Name
L1.2, L2.2, L2.3 3-phase mains connection to the commutation reactor
++, – –
Technical data of the connection terminals
M12
Figure 29:
6.3.3

External fan power supply

Connection Terminals
Voltage supply
Power input
Spare fuses
permissible connec-
tion cross-section
maximum tightening
torque
Figure 30:
GB - 78
Function
DC voltage output with starting current limiting;
Connection for inverter
Connection for shielding /earthing
Stay bolt for maximum 2 ring thimbles with
240 mm² for each
Connection terminals of the power circuit
+, -
+24 Vdc ±10 %
approx. 2.5 A per
module
3.15 A Type gG
minimum 50 V
0.2...4 mm²
24 ...10 AWG
0.6 Nm
5.3 lb inch
External fan power supply
L1.2
L2.2
++
--
PE
PE
PE
PE
max. tightening torque
48 Nm
+24Vdc / 3A
L3.2
400 lb inch
+