WIRE THE KEYPAD

Each keypad model has specific wiring assignments. All zones are supervised. The
maximum zone line impedance is 100 Ohms. Ground fault is detected at 1420 Ohms
or less. Locate the keypad model below and refer to Figure 3 to wire the keypad.

Model 7060-WINT and 7063-WINT

Use a 4-wire cable for panel keypad bus connection. See Wiring Specifications for
additional wiring information.

Model 7073-WINT

Use a 4-wire cable as needed for keypad bus and zone input connections. Use a
5-wire cable for external card reader connection. Use DMP Model 311 1k Ohm EOL
resistors on keypad zones 1-4. Connect the red wire to panel terminal 7, connect the
yellow wire to panel terminal 8, connect green wire to panel terminal 9, and connect
black wire to panel terminal 10.