WIRE THE ELECTRONIC LOCK
The 7073-WINT keypad provides a Form C (SPDT) relay for controlling locks
and other electronically-controlled barriers. The Form C relay draws up to 15 mA
of current and the contacts are rated for 1 Amp at 30 VDC maximum. The three
terminals marked NO C NC allow you to connect the device wiring to the relay for
module control. Use an additional power supply to power magnetic locks and door
strikes. See Figures 5a and 5b.
5
WIRE THE 333 SUPPRESSOR
Use the included 333 suppressor with the keypad to suppress any surges caused
by energizing a magnetic lock or door strike. Install the 333 across the keypad C
(common) and NO (normally open) or NC (normally closed) terminals. If the device
being controlled by the relay is connected to the NO and C terminals, install the
suppressor on the NO and C terminals. Conversely, if the device is connected to the
NC and C terminals, install the 333 Suppressor on NC and C terminals. See Figures 5a
and 5b.