Pin Assignments for Releasing Module
18.4
18.4.1 X5 plug connection for releasing relay output
Indicators
18.5
18.5.1 LED indicators
LED
Color
H1
Green
H2
Green
H3
Green
Siemens Industry, Inc.
Building Technologies Division
Pin
Designation
4
REL_CIR1 (+)
3
REL_CIR1 (-)
2
REL_CIR2 (+)
1
REL_CIR2 (-)
Admissible cable cross-section: 12...18 AWG, unshielded
REL_CIR1
REL_CIR1
REL_CIR2
REL_CIR2
*REL-EOL: Terminating resistor 24 kΩ and diode (Siemens part
number 500-696359)
Function
Status of releasing circuit 1
Status of releasing circuit 2
Status of processor
FS20 Marine Fire Detection Control Panel
Description
Relay output for releasing 1
Relay output for releasing 1
Relay output for releasing 2
Relay output for releasing 2
X5
+
4
- 3
+
2
- 1
Condition
Definition
Off
Releasing circuit 1 inactive
On
Releasing circuit 1 activated
Off
Releasing circuit 2 inactive
On
Releasing circuit 2 activated
Off (steady)
Processor is not running
Flashing
Processor is running
On (steady)
Processor is not running
*
REL_EOL
*
REL_EOL
101
A6V10519176_enUS_b